PURPOSE

The device is designed for heat supply of residential premises and buildings for communal and domestic purposes, equipped with water heating systems with a water column height in the water circuit no more than 6.5 m.
The device is designed for continuous operation on natural gas in accordance with GOST 5542-87.
The device is manufactured in climatic version UHL, category 4.2 in accordance with GOST 15150-69.

Characteristics Safety devices
  1. Special design of the heat exchanger, the use of quality material:
    a) durability;
    b) high efficiency;
    c) reliability.
  2. Stainless steel burner
  3. Optimal combustion chamber
  4. Temperature control
  5. Ease of installation and maintenance
  6. Polymer staining
  7. Reliability
  8. Repairability
  1. Thermostat to prevent overheating of the heat exchanger
  2. Gas supply shutdown in case of extinction (flame supervision)
  3. Shutdown in the absence of traction
  4. Stabilizer for wind gusts
  5. Low boiler casing temperature

SPECIFICATIONS

Parameter or size name The quantity
AOGV 11.6-1 AOGV 17.4-1 AOGV 23.2-1
1. Fuel Natural gas
2. Nominal pressure of natural gas in front of the automation unit, Pa (mm.w.st.) 1274 (130)
Natural gas pressure range, mm.w.st. 65…180* 1
3. The volumetric content of carbon monoxide in dry undiluted combustion products of natural gas,% no more 0,05
4. Coefficient of efficiency of the device,% not less 89
5. Heat carrier water
6. Heat carrier parameters, no more:
0,165
- absolute pressure, MPa;
- maximum temperature, ºС 95
- carbonate hardness, mg-eq / kg, no more 0,7
- content of suspended solids absent
7. Rated thermal power of the automatic burner, kW (kcal / h) 11,6 (10000) 17,4 (15000) 23,2 (20000)
8. Size of the gas inlet connection:
- nominal bore DN, mm 15 20 20
G 1/2 -B G 3/4 -B G 3/4 -B
9. Safety automation parameters
- gas supply cut-off time for
pilot and main burners, sec
- when the gas supply is cut off or there is no
flame on the ignition burner, no more
60
- in the absence of draft in the chimney, no more, no less 10
10. Vacuum in the chimney behind the device, Pa 2.94 to 29.4
mm. water Art. from 0.3 to 3.0
11. Nominal bore of water connecting pipes DN, mm 40 50 50
- thread according to GOST 6357 - 81, inch G 1 1/2 -B G 2 -B G 2 -B
12. Weight of the apparatus, kg, no more 45 50 55
13. Heated area, m 2, no more 90 140 190
14.Capacity of the heat exchanger tank, liter 39,7 37,7 35
15. Maximum temperature of combustion products discharged into the chimney, ° С (gas pressure 180 mm.w.) 130 160 210
* 1 NOTE. The device is protected against emergency supply of inlet gas pressure up to 500 mm. water Art. gas valve design.

DEVICE AND PRINCIPLE OF OPERATION.

The device consists of the following units and parts: a tank - a heat exchanger, a main burner, an ignition burner unit with a thermocouple and an ignition electrode installed in it, a combined gas valve (multifunctional regulator), a weight stabilizer, and lining parts.

In the upper part of the tank - heat exchanger, a thermostat sensor is installed, connected by a capillary tube to the actuator of the thermostatic valve (system "bellows - thermo bulb"), and a thermometer sensor

The design feature of the 630 EUROSIT combination valve is the presence of a device for stabilizing the gas outlet pressure, as well as the combination of valve control in one handle with the designation of positions by the corresponding symbols and numbers on its end and an indicator on the valve cover. The dependence of the heated water temperature on the position of the control handle scale is shown below:

The operating principle of the temperature controller is based on the expansion of the liquid when heated. The working fluid, being heated in the sensor (thermal bulb) from the water in the tank - heat exchanger, heated by the combustion of natural gas, expands and flows through the capillary tube into the bellows, converting the volumetric expansion into a linear movement of the mechanism that drives the system of two valves (instantaneous and metering ). The design of the mechanism provides protection against thermal overload, which protects the system "bellows - thermal bulb" from damage and depressurization.

  1. When the required water temperature in the device is set with the control knob to increase, the instant (click) valve opens first, then the dosing valve.
  2. When the water temperature in the device reaches the set value, the dosing valve smoothly closes, transferring the main burner to the "low gas" mode.
  3. When the temperature rises above the set one, an instant (click) valve is triggered, completely shutting off the gas to the main burner.
  4. In the absence of draft in the chimney, the exhaust gases from the furnace heat the draft sensor, the sensor is triggered by opening the normally closed contacts of the thermocouple circuit. The solenoid (inlet) valve closes and shuts off gas access to the main and pilot burners. The thrust sensor is designed to be triggered during the absence of thrust for at least 10 seconds.
  5. When the gas supply from the mains is interrupted, the ignition burner instantly goes out, the thermocouple cools down, the solenoid valve closes, blocking gas access to the main and pilot burners. When the gas supply is resumed, the passage through the apparatus is completely closed.
  6. When the gas pressure in the network drops below 0.65 kPa, the gas pressure on the pilot burner will also drop, the emf of the thermocouple will drop to a value that is insufficient to hold the valve. The solenoid valve will close and shut off gas access to the burners.

PLACEMENT AND INSTALLATION

The placement and installation of the apparatus, as well as the supply of gas to it, is carried out by a specialized construction and installation organization according to the project agreed with the operating enterprise (trust) of the gas economy.

The room where the device is installed must have free air access from the outside and a ventilation hood near the ceiling.

The temperature of the room in which the device is installed should not be lower than +5 ºС.

The choice of a place for the installation of the device should be made in accordance with the instructions of safety measures set forth in section 7 of this passport.

The device is installed against non-combustible walls at a distance of at least 10 cm from the wall.

  1. When installing the device against a fire-resistant wall, its surface must be insulated with a steel sheet over an asbestos sheet with a thickness of at least 3 mm, protruding 10 cm beyond the dimensions of the case. There must be a passageway at least 1 meter wide in front of the apparatus.
  2. When installing the device on a combustible floor, the floor must be insulated with a steel sheet over an asbestos sheet with a thickness of at least 3 mm. The insulation should protrude 10 cm beyond the dimensions of the case.

Before starting the installation, it is necessary to de-preserve the device, check the correctness of its assembly in accordance with Fig. 1 and fig. 8 of this passport, and make sure that all parts and assembly units are securely and completely secured.

Connect the device to the chimney, gas pipeline and pipes of the heating system. The connecting pipes of the pipelines must be precisely matched to the location of the inlet fittings of the apparatus. The connection should not be accompanied by mutual interference of pipes and apparatus assemblies.

SAFETY PRECAUTIONS

Persons who have studied this passport are allowed to service the device.

Installation and operation of devices must comply with the requirements of the "Rules for the construction and safety of operation of hot water boilers, water heaters and steam boilers with overpressure", as well as the requirements of the "Safety Rules for Gas Distribution and Gas Consumption Systems. PB 12 - 529 ", approved by the Gosgortekhnadzor of Russia.

The operation of the devices must be carried out in accordance with the "Fire safety rules for residential buildings, hotels, hostels, buildings of administrative institutions and individual garages PPB - 01 - 03".

The operation of the device is allowed only with operable safety and temperature control automatics.

Gas safety automatics should provide:

  1. Reducing the gas supply when the water temperature in the heating system reaches the set value.
  2. Turning off the gas supply to the main burner when the preset heating temperature is exceeded.
  3. Turning off the gas supply to the device in the following cases:
    • when the gas supply to the apparatus is interrupted (for a time not exceeding 60 seconds);
    • in the absence of draft vacuum or in the boiler furnace (for at least 10 seconds and not more than 60 seconds);
    • when the flame of the pilot burner goes out (for a time not exceeding 60 seconds).

When using the device, the hot water temperature should not exceed 95 ° C.

It is prohibited:

  1. operate the device with the heating system partially filled with water;
  2. use other liquids instead of water as a heat carrier **;
  3. install shut-off and control valves on the supply line and pipeline connecting the heating system with the expansion tank;
  4. operate the device in the event of a gas leak through the gas pipeline connections;
  5. use an open flame to detect gas leaks;
  6. operate the device in the event of a malfunction of the gas network, chimney or automation;
  7. independently eliminate malfunctions in the operation of the device;
  8. make any design changes to the apparatus, gas pipeline and heating system.

When the device is not working, all gas taps: in front of the burner and on the gas pipeline in front of the device - must be in the closed position (the valve handle is perpendicular to the gas pipeline).

All malfunctions during the operation of the apparatus on gas must be immediately reported to the emergency service of the operating enterprise of the gas economy.

If gas is found in the room, immediately stop supplying it, ventilate all rooms and call an emergency or repair service. Until the malfunction is eliminated, it is forbidden to light matches in the room, smoke, use

** It is allowed to use Olga's household heat carrier (manufacturer: ZAO Organic Products Plant) according to the instructions for use. After a period of operation, the coolant must be drained and disposed of.

Gas boiler AOGV-23 ZhMZ

Heating gas boilers AOGV-23.2 Station wagon produced by ZhMZ is a floor-standing gas one and two-circuit non-volatile unit equipped with an imported automation unit.

This design allows you to minimize the cost of heating equipment. The device runs on natural or liquefied gas (after replacing the nozzles).

Fig. 1. External view of the Zhukovsky boiler AOGV-23

The presence of the second circuit allows the use of universal boiler units for the simultaneous supply of heat and domestic hot water supply.

Small dimensions, light weight and convenient shape make these boilers an ideal choice for installing an autonomous heating system in small spaces.

Advantages of gas Zhukovsky heating boilers

Heat exchanger

High efficiency of boilers (up to 89%), ensured by the tubular design of the heat exchanger with built-in turbulators;

High reliability of the heat exchanger tank due to the use of an automatic welding process and seamless seamless pipes;

Stable supply of hot water for domestic needs in a copper flow-through secondary circuit;

The possibility of using the devices in heating systems with natural and forced circulation of the coolant.

Automation

Safety, reliability, simplicity and ease of operation of boilers are ensured by the use of modern imported automation units;

Saving gas consumption due to the automatic modulation of the burner power in units with imported automation;

Convenience of control due to the optimal arrangement of automation units.

Burner

Ecological cleanliness due to the low content of nitrogen and carbon oxides in waste gases;

Stable operation of the device at low gas pressure in the network (up to 550 Pa);

Ease of use due to easy replacement and cleaning of the burner.

Gas boiler design ZhMZ AOGV-23

Protective outer coating of the boiler with powder white enamel;

Boilers are cylindrical and rectangular, automation is located at the top or bottom;

Equipping boilers with a pointer thermometer and piezo ignition;

Technical characteristics of the gas Zhukovsky boiler AOGV-23

The efficiency of the device efficiency (with continuous operation),%, not less: 88

Gas type - natural / liquefied

Rated thermal power, W (Kcal / h) - 23260 (20000)

Gas consumption:

Natural, no more - 2.55
- liquefied, no more - 0.87

Chimney vacuum, Pa (mm wc) minimum / maximum - 2.94 (0.3) / 29.4 (3.0)

Ignition time, sec., No more - 60

Carbon monoxide index, vol. %, no more - 0.05

Range of maintaining the water temperature in the heat exchanger, С - 50-90

Burner type - Injection

Tank capacity, l - 59

Outside diameter of the connecting branch pipe of the gas exhaust device, mm - 135 ± 2

Water consumption in hot water supply mode when heated at t \u003d 35 0С l / min., Not less - 7.1

Water pressure in front of the device in the DHW system, kPa (kg / cm2)

Maximum - 588 (0.6)
- minimum - 14.7 (0.15)

Water pressure in the heating system, kPa, no more - 100

Distance:

From the floor to the axis of the gas pipeline inlet, mm - 716 ± 5
- from the floor to the end of the outlet pipe of the heat exchanger, mm - 1050 ± 5
- from the floor to the axis of the inlet pipe of the heat exchanger, mm - 292 ± 5
- from the floor to the axis of the inlet pipe of the coil, mm - 587 ± 5
- from the floor to the axis of the outlet pipe of the coil, mm - 927 ± 5

Overall dimensions, mm: height x width x depth - 1050 ± 5 x 420 ± 5 x 480 ± 5

Weight of the device (without packaging), kg, no more - 60

Maintenance of the gas boiler ZhMZ AOGV-23 Universal

Periodically, but at least once every six months (before the start of the heating season), check the accuracy of the thermostat setting.

Fig. 2. Automation of the gas boiler ZhMZ Universal

1. Gas magnetic valve; 2. Launcher button; 3. Arrow; 4. Adjusting knob; 5. Thermoregulator; 6. Bellows - thermal bulb; 7. Filter, 4. Adjusting knob;

If the thermometer readings differ from the temperature set by the adjusting knob 4 (Fig. 2) by more than ± 5 ° C, it is necessary to adjust:

Set the adjusting knob 4 (Fig. 2) to number 4;

Warm up the coolant in the unit to 50 ° C;

Slowly turn the adjusting knob 4 (Fig. 2) towards decreasing temperature until the gas supply to the main burner stops;

Unscrew the screw securing the adjustment knob and remove it;

Carefully install the adjusting knob by aligning the number 1 on the adjusting knob with the arrow 3 (Fig. 2) and tighten the screw securing the adjusting knob;

Make sure that the setting is correct at the moment the main burner is turned off when the correspondence between the temperature set using the control knob and the actual temperature of the heating medium of the device is achieved.

Malfunctions of the Zhukovsky boiler AOGV-23 and their elimination

1. Pressing the start button fails to ignite the igniter, the flame on the igniter goes out, comes off

Gas valve in front of the device is closed - Open the gas valve.

The hole in the pilot nozzle is clogged - Clean the hole with a 0.3 mm diameter wire.

Gas pressure below 635 Pa (65 mm H2O) - Notify the gas utility.

Strong drafts in the room causing the ignitor flame to blow off - Eliminate or reduce drafts.

2. There is no spark between the spark plug electrode and the igniter

Large gap between electrode and igniter - Adjust gap.

Piezo ignition does not work - Replace piezo ignition.

3. When the start button is released (after holding it for at least a minute with the igniter on), the igniter flame goes out

Oxidation of the solder on the contacts at the joints of the electromagnet with the contact wire, weak pressing of the pins in the sockets - Unscrew the connector of the contact wire from the gas magnetic valve body, clean the contact with a needle file until it shines (remove the oxide film). Screw the union back into the body. Remove the sockets from the pins, lightly squeeze the sockets with pliers. Place the sockets on the pins. To avoid the destruction of the soldering of the contacts of the electromagnet and the wire of the contact, do not tighten the fitting of the wire tightly when screwing it into the gas magnetic valve body.

Draft sensor microswitch does not work - Replace microswitch.

The thermocouple does not generate EMF, the end of the thermocouple has burned out (the value of the EMF of the thermocouple must be at least 20 mV) - Replace the thermocouple.

The pilot flame does not touch the thermocouple - Position (bend) the thermocouple so that the flame washes over the end of the thermocouple (see Figure 3).

The safety thermostat is out of order - Replace the safety thermostat.

4. The flame of the burner and pilot is extinguished. Automatic shutdown of the gas supply during the operation of the gas boiler AOGV-23 ZhMZ. The thrust sensor is triggered

Complete or partial obstruction of the chimney - Clean the chimney.

Strong drafts in the room causing the ignitor flame to blow off - Eliminate or reduce drafts.

The pressure has dropped below 635 Pa (65 mm H2O) - Notify the gas utility.

To measure the gas pressure in the network, disconnect the pilot tube from the fitting on the valve body. Connect a measuring device to the nipple.

Turn the adjusting knob, setting it to 50 - 60 ° C. Press the start button all the way, then release it 2 - 3 mm and after 8 - 12 seconds. take readings of the device.

5. The response time of the automatic equipment of the gas Zhukovsky boiler AOGV-23 in terms of thrust is less than 10 sec. in the absence of draft in the chimney. The response time of the automatic thrust is more than 60 sec. in the absence of draft in the chimney.

The draft sensor is not adjusted - Adjust the sensor, for which: unlock, unscrew (or tighten) the adjusting screw by 1-2 mm and re-lock it. Check the response time. Repeat the operation if necessary.

The response time depends on the gap between the adjusting screw and the microswitch button. As the gap increases, the response time increases and vice versa.

6. The main burner does not turn off

The "bellows-thermal bulb" is depressurized - Replace the "bellows-thermal bulb"

Thermostat is out of alignment - Adjust the thermostat for response ranges between 50-90 ° C.

7. After shutdown, the burner does not turn on for a long time. The water in the tank is hot, the batteries are cold

No circulation in the heating system - Eliminate reverse slopes in the heating system. Eliminate air cushions in the heating system.

8. The presence of a flame on the firing holes of the main burner when the thermostat is turned off

Leakage of the thermostat valve due to dirt - Remove the front thermostat cover. Clean the valve plug and apply sealing grease.

9. Traction chopper door does not rotate or rotates tightly

Dirt on the door pivot - Remove any dirt from the door pivot and the axle seat in the traction chopper body.

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

__________________________________________________________________________

_______________________________________________________________________________

__________________________________________________________________________

OPERATION AND REPAIR OF BOILERS

The most affordable energy resource with a minimum level of harmful emissions in the modern world is gas. The use of AGV for space heating is the most effective option in terms of efficiency and safety. Independence from power supply and low cost services allow water heaters to take their rightful place among similar devices.

Water heating boilers AGV, using gas as an energy carrier, began to be produced by ZhMZ (Zhukovsky Machine-Building Plant) since 1967. The new generation of gas heaters is capable of heating housing up to 140-200 m², the equipment can also be used to provide hot water. TO slugs are equipped with a reliable automatic gas control system.

The products of ZhMZ are now represented by about 30 types of boilers. Among them are modifications with a capacity from 11 kW to 68 kW - AOGV, KOV, AKGV. Certified devices that have permission to manufacture and use are capable of heating up to 610 m² of area.

The principle of operation of AGV

The basis of the design of AGV devices is a cylindrical tank connected by a pipeline system with the entire heating network of the house. A heat exchanger is located inside the cylinder - a flame tube heated during gas combustion. In the AGV-80 and AGV-120 devices, a turbulator was placed inside, which slightly increased the efficiency of the installation.

The heating system is a network of an ascending pipe, radiators, an expansion tank and a return pipe.

This system provides full cycle of the devicewhich includes:

  • heating the coolant - water;
  • the rise of the heated coolant along the ascending pipeline to the heating devices - radiators;
  • heat release;
  • return water return to the device for subsequent heating.

A thermosiphon heating system (or a natural circulation system) does not require additional installation of pumps, and compensation for water losses comes from an expansion tank. Waste gas combustion products enter the chimney and are removed to the atmosphere.

IMPORTANT! The AGV system allows you to install a pump to provide forced water circulation. Such a boiler will no longer be considered non-volatile, since electricity is needed for the pump to function.

The AGV-80 and AGV-120 devices were equipped with an automatic device that prevented the flow of energy when a certain temperature was reached, with spontaneous attenuation of the burner wick, a decrease in draft in the chimney, or with a decrease in gas pressure in the main line.

When the temperature of the coolant decreases, the automatic sensor is triggered, turning on the gas supply to the burner.

New generation AGV devices are distinguished by a more efficient design, but all heat and water heating systems operate in the mode of a conventional gas boiler. Structural differences lie in the division of the flame tube into separate sections. And also a coil for preparing hot water is mounted in the water jacket.

The technical parameters of the operation of the first and one of the latest modifications of AGV boilers are presented below:

Thermal power Heated area Tank capacity Efficiency Maximum water heating temperature
AGV-80 7 kW up to 60 m² 80 l 75% 90˚ 85 Kg
AOGV-23.2 23.2 kW up to 200 m² 35 l 89% 95˚ 55 kg

Advantages and disadvantages

Serious significant advantage, which favorably distinguishes AGV gas boilers from similar equipment, is their independence from the supply of electricity, in other words, there is no need for. Others "Pluses" the use of devices is recognized:

  • affordable price;
  • high efficiency indicators: the obtained effect from use significantly exceeds the costs of ensuring the functioning of the boiler;
  • reliability and safety of boiler operation;
  • ease of maintenance.

Available advantages cannot smooth out the characteristic "Cons" that have a negative impact on the characteristics of the equipment:

  1. This is a low efficiency factor;
  2. Equipping with unreliable automation;
  3. Significant dimensions of the devices themselves and the large diameter of the pipes;
  4. The need for strict adherence to the slopes of the pipes during their installation.

Knowing the strengths and weaknesses of the equipment, you can reasonably approach the choice.

Choosing an AGV (gas boiler) for a private house

Features of the house (area, used building materials) and climatic characteristics of the area - one of the main criteria for a successful choice heating device and hot water supply. The second important feature is the power of the boiler.

Important! Multiplying the power value by 10 m² of area will tell you what area the boiler can heat. For regions with a harsh climate, it is necessary to provide a power reserve of 25%.

The criterion that determines the choice is the price of equipment, as well as the cost of materials required for operation. Compared to imported counterparts, domestic devices are ≈ 35% cheaper, the cost of maintenance is also three times lower.

Gas boiler AOGV-11.6 and AOGV - 23

The AOGV-11.6 apparatus is a floor-mounted modification of equipment from the assortment range of single-circuit boilers of the Zhukovsky Machine Plant (ZhMZ). Designed exclusively for heating needs. Its marking stands for "gas water heating apparatus". The next figure in the brand designation indicates its power - 11.6 kW.

Models AOGV-11.6-3 ("Economy" and "Universal") refer to double-circuit boilers and can provide the consumer, in addition to heating, also with hot water. With single-circuit devices, these boilers differ in the presence of a steel coil in the structure.


They differ among themselves in the features of automatic systems (the first of these is equipped with domestic automation, "Universal" works with the Italian system).

Modern gas boiler AOGV - 23 are distinguished not only by an improved appearance, but also by the modernization of some structural elements:

  • durable Italian thermometers were installed instead of unreliable domestically produced glass instruments;
  • automation system of the American company Honeywell allows you to monitor the smoke exhaust system, maintain heating, turn off the gas in case of breakdowns in the system, in the absence of a burner flame, it blocks the operation of hot water equipment;
  • equipment with an injection burner allows for the most complete combustion of gas without residue.

The use of a new technology for coating the metal surface of the boiler drum has ensured an attractive appearance of the equipment. This makes AGV (gas boilers) a good choice for a private house or summer cottage.

Important! The boiler room can be located anywhere, but not in a residential area. It is imperative to provide for the possibility of air inflow and outflow in the furnace.

Installation of equipment in accordance with certain technical standards and safety requirements can be carried out by a specialized organization. The exact implementation of all rules, instructions and recommendations for the installation of the boiler is checked by a representative of the gas inspection.

Important! The inspector will give permission to connect the equipment to the mainline in case of full implementation of all the requirements of the project documentation, ensuring safety.

The gas boiler Rostovgazoapparat AOGV 23.2-1 is a floor-standing gas boiler with a capacity of 23.2 kW designed for heating residential, industrial, warehouse premises with a total area of \u200b\u200bup to 230. The AOGV series boiler is a single-circuit boiler, without the possibility of preparing hot water. AOGV is one of the very first boilers that were installed in the private sector. Most users have had these boilers for 20 years. When replacing a gas boiler, the last thing you want to do is to redo and digest your heating, AOGV boilers are manufactured in accordance with GOST while maintaining the connection parameters.

AOGV are serviced by all Gorgaz services.

Technical equipment of the Rostovgazoapparat boiler:
Cylindrical heat exchanger made of high-quality carbon structural steel;
Automation unit (Rostovgazoapparat);
Round atmospheric steel burner (Rostovgazoapparat);
Coloring the body in an electrostatic field

Model AOGVK
11,6
AOGVK
11,6
AOGV
17,4
AOGVK
17,4
AOGV
23,2
Rated thermal
power, kWt
11,6 11,6 17,4 17,4 23,2
Reduced gas consumption
natural, m3 / h
1,18 1,18 1,76 1,76 2,3
Approximate area
heating, m2
125 125 100-200 100-200 100-250
Flue gas efficiency,
%, not less
90 90 90 90 90
Water consumption in mode
hot water at
heating at? t \u003d 35 ° C, l / min
3,5 3,5
Connecting thread
connection for feeding
gas, inch
G? G? G? G? G?
Lead in / out
to the heating part
to the water heating part
G1? G1?
G?
G1? G1?
G?
G1?
Inner diameter
gas outlet pipe,
dm, not less
1,15 1,15 1,25 1,25 1,38
height 865 865 865 865 850
width ?410 ?410 ?410 ?410 330
depth 550
weight 43 47 49 52 56

The gas boiler Rostovgazoapparat AOGV 23.2-1 is a floor-standing gas boiler with a capacity of 23.2 kW. Buy gas boiler Rostovgazoapparat AOGV 23.2-1 in Minsk at st. Installers 9. You can also use the service of delivery of the boiler gas boiler Rostovgazoapparat AOGV 23.2-1 across Belarus. You can find out the price, compare prices, specifications, parameters on the website, the managers of our store will help you choose the necessary and reliable equipment.
Delivery of the gas boiler Rostovgazoapparat AOGV 23.2-1 is carried out in all cities of Belarus (Minsk, Berezino, Gorodeya, Ivenets, Krupki, Molodechno, Radoshkovichi, Smilovichi, Stolbtsy, Bobr, Dzerzhinsk, Kletsk, Logoisk, Negoreloe, Rudensk, Uzda Smolevichi , Borisov, Zhodino, Kopyl, Lyuban, Nesvizh, Svir, Soligorsk, Urechye, Vileyka, Zaslavl, K. Sloboda, M. Gorka, Pleschenitsy, Svisloch, Starobin, Fanipol, Volozhin Zel. , Cherven, Grodno, Berezovka, Stomach, Krasnoselsky, Novogrudok, Ross, Shchuchin, B. Berestovitsa, Zelva, Lida, Novoelnya, Smorgon, Yuratishki, Volkovysk, Ivye, LyubOstrino, Svisloch, Voronovo, Kozlovshchina, Mir, Oshmyany, Skidel , Korelichi, Bridges, Porozovo, Slonim, Gomel, Belitsk, Yelsk, Kopatkevichi, Oktyabrsky, Svetlogorsk, Buda-Koshelev, Zhitkovichi, Korma, Parichi, Streshin, Vasilevichi, Zhlobin, Mozyr, Petrikov, Uvarovichi, Vetka, Zarechye , Khoiniki, Dobrush, Kalinkovichi, Ozarichi, Rogachev, Chechersk, Mogilev, B Elynichi, Gorki, Osipovichi, Bobruisk, Dribin, Slavgorad, Bykhov, Kirovsk, Chausy, Glusk, Klichev, Cherikov, Glusha, Krugloye, Shklov, Brest, Antopol, Gantsevichi, Ivatsevichi, Luninets, Ruzhany, Baranovichi, Kamovichi Telekhany, Beloozersk, Drogichin, Kobrin, Mikashevichi, Shereshevo, Birch, Zhabinka, Kossovo, Pinsk, Vysokoe, Ivanovo, Logishin, Pruzhany, Vitebsk, Baran, Borovukha, Dokshitsy, Novolukoml, Podvilye, Begoml, Novolukoml, Podvilye, Begoml, Vetrino, Dubrovkol Beshenkovichi, Voropaevo, Kokhanovo, Obol, Postavy, Bogushevsk, Glubokoe, Lepel, Orekhovsk, Bolbasovo, Gorodok, Liozno, Orsha, etc.)

    Model ZhMZ AOGV-23,2-3 Universal, (N) Is a single-circuit heating boiler made of modern durable materials and equipped with the latest high-tech internal equipment. The boiler is designed to work in a domestic environment, it has simple control and does not require serious maintenance. It can work in different types of heating systems.

    Features and Benefits:

    • Refined design.
    • Non-volatile boiler.
    • Italian automatic equipment EuroSit.
    • It is allowed to use softened water or household antifreeze such as Dixis, Teply Dom as the heat carrier of the heating system.
    • It runs on natural (main) gas, after replacing the injectors it can run on propane.
    • Low content of nitrogen oxides and carbon in waste gases, environmentally friendly.
    • Ease of use due to easy replacement and cleaning of the burner.
  • Specifications

    Brand nameZhukovsky
    Build countryRussia
    Boiler typegas
    Number of contourssingle-circuit
    The combustion chamberopen
    Type of fuelNatural gas, LPG
    Installationoutdoor
    Heated area200 sq. m.
    Power23.26kW
    Efficiency%88
    Controlmechanical
    Country of originRussia
    CondensingNot
    19.5kw
    Non-volatileYes
    Primary heat exchanger materialsteel
    Liquefied gas consumption, kg / hour1.74
    Natural gas consumption cub. m / hour2.55
    Nominal pressure of natural gas, mbar12.7
    Nominal pressure of liquefied gas, mbar29.4
    Heat carrier temperature, ° С50 - 90
    Max. water pressure in the heating circuit, bar1
    Color
    Warranty period2 years
    ModelZhukovsky Universal AOGV

    Connection and dimensions

    You can pay for the product in the following ways:

    Cash payment is possible when purchasing goods in our office, or when delivered to your home or to a pick-up point.

    A legal entity can pay for the goods by invoice, or by an agreement sent by e-mail / fax. To issue an invoice when ordering, you must specify all the details. Delivery is carried out only on full prepayment.

    If you are an individual, then the purchase can be paid through any bank operating in the Russian Federation. Contact our manager for the invoice. After receiving the invoice by e-mail or fax, you must pay for the goods within three working days.

    You can pay for an order with a card: - during the purchase in our office; - to the courier upon delivery; - through the payment terminal at the pick-up point; - when ordering online through the online store. Important: when paying via the Internet, contact our manager in order to clarify the availability of goods in stock!

    In our store you can buy any product worth more than 10,000 rubles on credit. To do this, click the "Buy on credit" button in the product card and fill out the application. To clarify the details, please contact the bank employees and our managers.

    For each purchase in our store, you will receive bonuses, accumulating which, you can later pay up to 100% of the cost of the goods. You can pay with bonus points during the checkout process by ticking the appropriate box.